Short description
I/O module | 8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B2 digital outputs, 24 VDC, 50 mA, OSSD <500 µs, SafeLOGIC-X technology |
General information
Safety characteristics
Note | See section "Safety characteristics". |
Safe digital inputs
Safe digital HS-LS outputs
Safe digital HS-HS outputs
Quantity | 2 |
Variant | FET, 2x positive switching, type B2, output level readable |
Nominal voltage | 24 VDC |
Nominal output current | 50 mA |
Total nominal current | 100 mA |
Output protection | See section "Inrush current behavior for output channels". |
Braking voltage when switching off inductive loads | Max. 45 VDC |
Error detection time | 1 s |
Insulation voltage between channel and bus | 500 Veff |
Peak short-circuit current | See section "Inrush current behavior for output channels". |
Leakage current when the output is switched off | <1 mA |
RDS(on) | 35 Ω |
Switching voltage | I/O power supply minus voltage drop due to RDS(on) |
Max. switching frequency | See section "Inrush current behavior for output channels". |
Test pulse length | Max. 500 µs |
Max. capacitive load | 100 nF |
Pulse outputs
Operating conditions
Mounting orientation | |
Horizontal | Yes |
Vertical | Yes |
Installation elevation above sea level | 0 to 2000 m, no limitation |
Degree of protection per EN 60529 | IP20 |
Ambient conditions
Temperature | |
Operation | |
Horizontal mounting orientation | 0 to 60°C |
Vertical mounting orientation | 0 to 50°C |
Derating | See section "Derating". |
Storage | -40 to 85°C |
Transport | -40 to 85°C |
Relative humidity | |
Operation | 5 to 95%, non-condensing |
Storage | 5 to 95%, non-condensing |
Transport | 5 to 95%, non-condensing |
Mechanical properties
Note |
Order 2x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately. |
Pitch | 25+0.2 mm |
Número de material:
X20SLX842-1Descripción:
X20 SafeLOGIC-X controller (Safety+) 8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B digital outputs, 24 VDC, 50 mA, OSSD <500 µs
Accesorios obligatorios
Certificados | Versión (fecha) | Descargar |
---|---|---|
FS Certificate Safety+ | PDF / 930 KB |
Documentación | Versión (fecha) | Descargar |
---|---|---|
Data sheets SafeIO and SafeLogic | PDF / 30 MB | |
Integrated safety technology user's manual - mapp Safety | PDF / 62 MB |